Pengaruh Pembebanan Terhadap Efisiensi Transformator Distribusi Di PT. PLN (Persero) UP3 Garut

Main Article Content

Iqbal Fadillah
M. Reza Hidayat
Christiono
Handoko Rusiana Iskandar
Een Taryana

Abstract

Transformer efficiency is defined as the ratio of the incoming power to the outgoing electric power. Even so the ideal transformer has 100% efficiency, this ideal transformer does not exist, because the energy that goes out is always less than the energy that goes in, meaning that there is energy loss. Load imbalance in an electric power distribution system always occurs and the imbalance is in single-phase loads in low-voltage network subscribers. Due to the load imbalance, a current appears in the neutral of the transformer. Perform analysis and compare efficiency. Analysis of used load capacity is not efficient. Analysis of the results of current and voltage measurements at the substation to obtain efficiency, and transformer losses in day and night conditions using LWBP and WBP methods. In this study, observations were made regarding the transformer efficiency analysis using the Outside Peak Load Time (LWBP) and Peak Load Time (WBP) methods. The LWBP method is carried out during the day for 20 hours, while the WBP method is carried out at night for 4 hours, from 18.00 to 22.00. Then measurements were made at PT. PLN (Persero) UP3 Garut. For the highest percentage of loading which is close to the standard of 80%, namely the afternoon loading at the PDDK substation, which is 50.93%, the load used is 50.93 kVA. The night load at the CITL substation is 77.49%, the load used is 77.49 kVA. For the lowest percentage of loading that deviates from the standard 80%, namely the daytime loading at the SJRK substation, which is 16.32%, the load used is 16.32 kVA. The night load at the SJRK substation is 21.52%, the load used is 21.52 kVA. Based on observations, it is not efficient because the unused load is very large, it is recommended to use a smaller transformer capacity. The highest efficiency in the LWBP method is at the CITK substation 97.87%, the lowest at the PDDK substation 94.55%. The highest efficiency in the WBP method is at SJRK substations 95.5%, the lowest at PDDK substations is 92.1%.

Downloads

Download data is not yet available.

Article Details

How to Cite
Fadillah, I., Hidayat, M. R., Christiono, Iskandar, H. R., & Taryana, E. (2024). Pengaruh Pembebanan Terhadap Efisiensi Transformator Distribusi Di PT. PLN (Persero) UP3 Garut. SUTET, 13(2), 101–112. https://doi.org/10.33322/sutet.v13i2.1885
Section
Articles

References

Suryana, Alvian J, “Analisis Keandalan Transformator Distribusi menggunakan Indikator Tegangan Regulasidan Efisiensi Transformator (Studi Kasus pada PT.PLN APJ Jember)”, Universitas Jember, Mei 2012.

E. Julianto, “ Studi Pengaruh Ketidakseimbangan Pembebanan Transformator Distribusi 20 kV PT. PLN (Persero) Cabang Pontianak”, 2017.

Z. Syaroni, “Analisis Ketidakseimbangan Beban Transformator Distribusi 20 kV dan Solusinya Pada Jaringan Tegangan Rendah”, J. Teknik Elektro, vol 08, no. 01, pp. 173-180, 2019.

Wiranto, Ikhsan M, “Analisis Kinerja Transformator Distribusi Kawanua Emerald City-Amethys”, 2021.

Sumanto, “Teori Transformator”, 1991.

Syafriyudin, “Perhitungan Lama Waktu Pakai Transformator Jaringan Distribusi 20 Kv di APJ Yogyakarta”, 2011.

I. B. Tiasmoro, “Analisis Pengaruh Pembebanan Terhadap Efisiensi dan Susut Umur Transformator Step Up 6kV / 70kV di PLTU Sumbawa Barat Unit 1 dan 2 2x7 MW PT. PLN (PERSERO) UPK TAMBORA”, 2021.

T. O. Priyono, “Analisa Pengaruh Beban Tidak Seimbang Terhadap Efisiensi Transformator Distribusi”, 2017.

S. Nugroho, W. P, Sriyanto, Nor Chasanah, “Analisis Efisiensi Distribusi Listrik Unit Pelayanan Jaringan Dengan Metode Data Envelpment Analysis (DEA) Studi Kasus di Area Pelayanan Jaringan Kudus, PT. PLN (Persero)”, 2011.

M. I. Singgih, E. A. Anggraini,“Analisis Efisiensi Teknis Dari Distribusi Listrik Menggunakan Data Envelopment Analysis (DEA) dan Analisi Operasional”, 2008.

W. H. Pareira, “Analisis Pengaruh Beban Tidak Seimbang Terhadap Kualitas Daya pada Jaringan Distribusi Radial di Area Atambua Kabupaten Belu”. Institut Teknologi Nasional, Malang, 2017.

Hastungkoro, P.H., Wicaksono, W., & Widodo, T.S. “Transformator”, Klaten: Saka Mitra Kompetensi, 2019.

Afrianda, R., Samsurizal, S., & Nurul, A. A. Pengaruh Ketidakseimbangan Beban Terhadap Efesiensi Transformator Distribusi Studi Gardu PT PLN (PERSERO) Area Bekasi. SUTET, 10(1), 29-38. 2020.

SPLN 50 1997, “Spesfikasi Transformator Distribusi”, 1997.

S. Mochtar Wijaya, “Dasar-Dasar Mesin Listrik”, Jakarta: Djambatan, 2001.

SPLN 41-1 1991, “Persyaratan Penghantar Tembaga dan Alumunium Untuk Kabel Listrik Berisolasi”, 1991.

Sutjipto Rachmat, “Studi Pengaruh Pembebanan Sebagai Dasar Scheduling Maintenance untuk Meminimalisir Susut Umur Transformator 1 GI”, J. Sistem Kelistrikan, vol 07, no. 03, pp. 2407-2338, 2020.

M. D. T. Sogen, “Analisis Pengaruh Ketidakseimbangan Beban Transformator Gardu Distribusi JKL di PT. PLN (Persero) Area Ciputat”, STT-PLN, Jakarta, 2018.