Pengaruh Penambahan Liquid Suction Heat Exchanger Terhadap Performa Mesin Pendingin Menggunakan R404A

Main Article Content

Roswati Nurhasanah
Prayudi Prayudi

Abstract

One method to improve the performance of vapor compression refrigeration system using subcooling. The liquid line suction heat exchanger (LLHX)  sub-cooler is a method to increase the cooling capacity of the evaporator by lowering temperature at the condenser outlet. LLHX always Increased effect of refrigeration, work of compressor and heat rejected in the condenser. The results Showed that LLHX lowering condenser exit temperature and exit temperature compressor increases as a result of superheat. LLHX exit temperature compressor with stable at 28oC compared to 16oC on the operation without LLHX in 60 minutes. The experimental results also showed that the evaporation temperature decreases of 15.2 with the addition LLHX be 17.4oC. and the latter can increase the value of COP of 2.85 until 3.5.

Downloads

Download data is not yet available.

Article Details

How to Cite
Nurhasanah, R., & Prayudi, P. (2019). Pengaruh Penambahan Liquid Suction Heat Exchanger Terhadap Performa Mesin Pendingin Menggunakan R404A. JURNAL POWERPLANT, 4(2), 86–94. https://doi.org/10.33322/powerplant.v4i2.847
Section
Articles

References

Bolaji B.O., Performance of A R22 split-air-contioner when retrofitted with ozone friendly refrigerant (R410A and R417a), Journal of Energi in Southern Africa, Vol 23 No 3, pp 16-23, 2012
Bolaji B.O., Akintunde M.A., Falade T.O, Theoretical Onvestigation of the Performance of Some Envoronment-Friendly Refrigerants ins Sub-cooling Heat Exchanger Refrigeration Sistem , Journal of Science and Technology, Vol 30, No. 3, pp.101-108, 2010
Bolaji B.O., Zhongjie H, Thermodynamic analysis of hydrocarbon refrigerants in a sub-cooling refrigeration sistem , Journal of Engineering Research, Vol 1 No 1 June 2013, pp. 317-333, 2013
Poltker G., Hrnjak P.S, Effect of Condenser Subcooling of the Performance of Vapor Compression Sistem s:Experimental and Numerical Investigation, International Refrigeration and Air Conditioning Conference, July 16-19, 2012, Purdue e-Pubs, 2012.
Paharia A.K., Gupta R.C., Effect of Sub Cooling and Superheating on Vapor Compression Refrigerator Sistem s Using R-22 Alternative Refrigerants, International Journal od Emerging Trnes in Engineering and Development, Issue 3, Vol 1 Januari 2013, ISSN : 2249-6149, 2013
Arijanto dan Ojo Kurdi, 2010, Pengujian Refrijeran Hycool HCR R22 pada AC Splite sebagai Pengganti Freon R22, Rotasi, Volume 2, April 2010, hal 42-46
XU L., HRNJAK P., Potential for Improving Efficiency by Controlling Subcooling in Residential A/C System, International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 2014, Paper 2387, 2014
Thangavel P., Somasundaram, Effects Ovaporator loas on vapor compression refrigeration sistem using eco friendly hydrocarbon refrigerants with sub cooling, Journal of Scientific and Industrial Recearch, Vol 72, November 2013, pp. 695-702, 2013
Thangavel P., Somasundaram P., Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants, International Journal of Engineering and Innovative Technology, Volume 2, Issue 10, April 2013, ISSN : 2277-3754 pp. 127-131, 2013
Nuriyadi M, Sumeru . The Effect Of Liquid Suction Heat Exchanger Sub-cooler on Performance Of A freezer Using R404A as Working Fluid. Jurnal Teknologi. 76:11, 2015